Did you know there is a requirement for your arc flash evaluation report? Just as we have requirements for calculating arc flash values (i.e. OSHA, NFPA 70E, IEEE 1584), there is also a requirement for reporting. The standard is called: IEEE 1584.1-2022 - IEEE Guide for the Specification of Scope and Deliverable Requirements for an Arc-Flash Hazard Calculation Study in Accordance with IEEE Std 1584
The following items are recommended by IEEE 1584.1 to be provided in the final report:
Include reference to any other studies that may have been used or performed in conjunction with the arc flash hazard calculations, such as coordination, short circuit or equipment studies. Any assumptions should be denoted and of course the results of the study.
Description of the scenarios or modes of operation need to be called out. Arc flash hazard calculations should include such items as equipment ID, bolted fault current, arcing fault current, arcing duration, arc flash boundary distance, incident energy level and working distance.
Documentation of the input data, i.e. utility information, their modes of operation, fuse types, circuit breakers, clearing times etc.
One line drawings (also known as single line drawings). These may contain details for each of the items in scope and names should match the tables included in reporting.
Documentation of the software used to perform the studies.
The 1584.1 standard is a great minimum requirement for arc flash reporting but Rozel also includes color-coded prioritized recommendations to reduce arc flash hazards, improve overcurrent protective device coordination, identifies overdutied breakers and denotes when improper installations are observed.